Electrical tubing and slab reinforcement: the placement of the pipes for the electrical installation must be done once the reinforcement grid is finished; before, the exact location of the boxes and descents must be traced in the form. the placement of the reinforcement should be done foreseeing that no rod coincides with any lighting box; if they coincide, deviations will be made to the reinforcement in the form of a horizontal swing with a minimum separation of 20 cm to the center of the box. to achieve a good connection of tubes to boxes; it is necessary to make the pipes a soft doubles; as much as the rods allow. the bending of the rods will preferably be done in a bench to obtain the indicated upper and lower coatings. in the same cross section of slab; it should not overlap more than a third of the reinforcement. no more than two contiguous overlaps in slabs will be left; having to alternate with the adjacent rods. the saddles will receive the transversal reinforcement. autocad - dwg.